High THDi — total harmonic distortion of current — is the ratio of the RMS value of all current harmonics to the fundamental current, expressed as a percentage. It rises when nonlinear loads such as variable frequency drives (VFDs), rectifiers, UPS units and chargers draw current in pulses instead of a clean sine wave. A high reading must be explained, not simply cleared: measure the s...
Harmonics are extra currents and voltages at integer multiples of the supply frequency that non-linear loads draw on top of the fundamental sine wave. Their effect is costly: transformers, motors and neutral conductors overheat, relays mis-trip, and equipment life shortens even below rated load. This guide covers measurement at the point of common coupling (PCC) and how to compare the main mitigat...
An Active Harmonic Filter (AHF) is a parallel-connected, closed-loop power-electronic device that measures load harmonic current with current transformers and injects an opposing current to cancel distortion at the point of common coupling (PCC). The engineering conclusion is blunt: an AHF is selected against the measured harmonic spectrum, load variability, site ambient temperature, and network i...
Neutral conductor overheating in a three-phase four-wire system is a zero-sequence problem, so measure harmonic orders first and only then select a filter. A neutral that runs hot while the phases stay comfortably cool is rarely a coincidence. It points to zero-sequence current driven by triplen harmonics, which behaves nothing like a balanced-load calculation predicts. This article follows the or...
Capacitor bank overheating after adding VFDs is a power quality symptom, not a capacitor defect. VFD rectifiers inject harmonic current, the bank offers a low-impedance path at those frequencies, and parallel resonance between the bank and the supply can amplify that current until fuses open, contactors chatter and capacitor cans swell. A capacitor bank supplies reactive power to correct power fac...