Understanding the significance of power quality in the context of motor and electrical equipment efficiency is crucial. Power quality is evaluated through several key parameters, including harmonics, voltage unbalance, and voltage fluctuations. In an alternating current (AC) system, the interaction between voltage potential and current through the load circuit is described by frequency and amplitude.The current frequency will match the voltage frequency if the load's resistance or impedance doesn't change. In linear loads, such as resistors, capacitors, or inductors, where the current and voltage share the same frequency, the system behaves predictably.
However, non-linear loads, like switching power supplies, transformers that saturate, charging capacitors, and converters used in motor drives, introduce variability. As the voltage amplitude fluctuates and the load impedance changes, the frequency of the current also varies, creating a complex current waveform.
Harmonics are additional voltage and current frequencies that overlay the standard sinusoidal voltage and current waveforms. These frequencies are typically integral multiples of the base frequency, which is 50 Hz in many parts of the world. Harmonics are generated by non-linear loads, often referred to as "switching loads," because the current does not vary smoothly with voltage as it would in simple resistive or reactive loads. Every time the current is turned on and off, a current pulse is produced, resulting in a pulsed waveform that contains a spectrum of harmonic frequencies, including the fundamental 50 Hz and its multiples.
The higher-frequency waveforms, collectively known as total harmonic distortion (THD), do not perform any useful work and can be problematic. While the distorted current caused by non-linear loads has a minimal effect on other loads within a facility, its impact on distribution systems can be severe due to increased current flow, leading to higher losses in both customer and utility power system components.
Sources of harmonics include a variety of non-linear loads:
- Static power converters and rectifiers found in uninterruptible power supplies (UPS), battery chargers, and similar applications.
- Arc furnaces used in metal processing.
- Power electronics for controlling motors, such as AC and DC drives.
- Computers and other electronic devices.
- Saturated transformers, where magnetic saturation can cause non-linear behavior.
- Fluorescent lighting, particularly older ballast designs.
- Telecommunications equipment, including switches and amplifiers.
The effects of harmonics on various network elements are manifold. When harmonic currents pass through equipment:
- They cause additional losses due to their higher frequency. Devices with laminated cores, like motors and transformers, experience higher losses because of the higher frequency of the harmonic current.
- In cables, the skin effect causes harmonic currents to flow along the outer skin of the conductor, leading to overheating.
- Harmonics can trigger false tripping of protective relays and the failure of capacitors installed in the distribution system for power factor correction.
- Certain harmonic currents, such as the 5th harmonic, have a reverse phase sequence, which can result in inaccurate meter readings. Similarly, in a network with significant harmonic pollution, a conventional induction motor may not generate sufficient torque due to harmonic currents producing counteracting torque.
- Higher order harmonics can interfere with telecommunications systems. When a telephone line runs parallel to a power line carrying harmonics, it can introduce noise into the telephone line, a phenomenon known as telephonic interference.
- A heavily polluted voltage waveform can lead to the malfunction of devices such as thyristors, whose operation depends on the zero crossing of the voltage waveform. This can result in commutation failures in thyristors.
- High harmonic content leads to a lower power factor. The displacement power factor is determined by the angle between the fundamental component of current and voltage, while the total power factor is affected by the presence of harmonic currents. In linear loads, the power factor and displacement power factor are equal, but for loads generating significant harmonics, the total power factor is significantly lower.
- Zero-sequence currents, such as third harmonic currents, tend to flow in the neutral wire of a three-phase, four-wire system. Most domestic and commercial loads that are non-linear in nature generate substantial amounts of third harmonic current, which can overheat the neutral conductor and potentially melt it. Under extreme conditions, the neutral current can surpass 1.5 times the normal line current.
- Harmonic currents can affect generators as well, especially those operating at maximum capacity without significant margin to absorb the additional heating losses caused by harmonic currents. Such losses can degrade the insulation of electrical equipment over time.
The cumulative impact of these effects highlights the importance of monitoring and managing harmonics to ensure optimal power quality and system reliability. By mitigating harmonics, one can prevent equipment damage, reduce energy waste, and improve the overall performance of electrical systems.
YTPQC-AHF
Active Harmonic filters are highly effective in addressing and resolving the aforementioned harmonic issues. They are specifically designed to detect and counteract the negative impacts caused by harmonics, ensuring a more stable and clean power supply.
By actively filtering out the harmonic components, active power filters help to maintain the quality and integrity of the electrical system, minimizing the disturbances and potential damage that harmonics can bring. Their application is crucial in various industries and power systems to achieve optimal power performance and reliability.
Active Harmonic Filter works by continuously monitoring the current waveform and injecting compensating currents to cancel out the harmonics. The process involves:
If you want to know more about harmonics or have any other questions, please feel free to contact us:sales@yt-electric.com at any time. Our professional team will be dedicated to providing you with assistance.