Active Power Factor Correction(PFC) and dynamic reactive power compensation use power electronics-based systems (like IGBT inverters) to provide real-time, adaptive correction of power factor (PF) and reactive power (VAR) in electrical systems. These solutions are essential for modern industrial, commercial, and renewable energy applications with rapidly changing loads and harmonic distortions.
Measures real-time load current & voltage to compute required compensation.
Uses PWM-controlled inverters to inject opposite-phase reactive current to cancel lagging/leading VAR.
Adjusts instantly to load variations (unlike passive capacitor banks).
✔ IGBT-based Voltage Source Inverter (VSI) – Generates compensating current.
✔ DC Link Capacitor – Provides energy storage for reactive power injection.
✔ Control System (DSP/FPGA-based) – Calculates compensation in real-time.
Industrial: Variable-speed drives (VFDs), arc furnaces, welding machines.
Renewables: Solar/Wind farms (to meet grid PF requirements).
Data Centers: UPS systems, server farms with fluctuating IT loads.
✔ Faster response (milliseconds vs. seconds for capacitors).
✔ No risk of overcompensation (avoids leading PF).
✔ Works with harmonic loads (unlike traditional capacitors).
Continuously monitors load demand and injects precise reactive current to maintain target PF (e.g., 0.95–1.0).
Can absorb or generate VARs (inductive or capacitive) as needed.
Device | Principle | Best For | Response Time |
---|---|---|---|
STATCOM (Static Compensator) | IGBT-based VAR generator | Large industries, renewables | <1 cycle |
D-STATCOM (Distribution STATCOM) | Compact, for LV/MV grids | Weak grids, solar farms | <1 cycle |
Active Harmonic Filter (AHF) | Corrects PF + harmonics | Semiconductor plants, data centers | <1 ms |
SVG (Static VAR Generator) | High-efficiency, modular | Wind farms, steel mills | <10 ms |
Steel Plants: Arc furnaces cause rapid PF swings → STATCOM stabilizes grid.
Wind Farms: Provides low-voltage ride-through (LVRT) by injecting VARs during faults.
Data Centers: Prevents PF penalties due to server load fluctuations.
Feature | Passive (Capacitor Banks) | Active (STATCOM/AHF) |
---|---|---|
Response Time | Slow (seconds) | Fast (<1 cycle) |
Harmonic Handling | Fails with harmonics | Compensates harmonics |
Overcompensation Risk | Yes (leading PF) | No (adaptive control) |
Maintenance | Low (no electronics) | Higher (cooling, firmware) |
Cost | Low | High (but ROI in large industries) |
✅ Real-time adjustment – No delays like capacitor switching.
✅ No resonance issues – Unlike capacitors, won’t amplify harmonics.
✅ Supports bidirectional VAR flow (inductive & capacitive).
✅ Improves voltage stability – Critical for weak grids.
✅ Reduces transformer/kVA loading – Saves energy costs.
Problem: Multiple VFDs cause low PF (0.7) and harmonics (THD >15%).
Solution: AHF + STATCOM → PF improved to 0.98, THD <5%.
Problem: Solar inverters cause leading PF during low generation.
Solution: D-STATCOM injects lagging VAR to maintain PF = 0.95.
Problem: Server load swings cause PF fluctuations (0.8–0.9).
Solution: Active PFC module ensures PF > 0.95 at all times.
For stable, low-cost correction → Passive PFC (capacitors).
For fast, dynamic, harmonic-rich loads → Active PFC (STATCOM/AHF).
Best for industries with:
Rapid load changes (e.g., cranes, arc furnaces).
Strict PF regulations (utilities penalize <0.9 PF).
High harmonics (VFDs, rectifiers, IT loads).