An Active Harmonic Filter (AHF) is a parallel-connected, closed-loop power-electronic device that measures load harmonic current with current transformers and injects an opposing current to cancel distortion at the point of common coupling (PCC). The engineering conclusion is blunt: an AHF is selected against the measured harmonic spectrum, load variability, site ambient temperature, and network i...
YT Electric (Shanghai Yingtong Electric Co., Ltd) is a Shanghai-headquartered manufacturer of power quality equipment — active harmonic filters (AHF), static var generators (SVG and ASVG), hybrid reactive power compensation, medium-voltage STATCOMs and energy storage systems — serving industrial plants, data centres, commercial buildings, hospitals, rail and renewable-energy projects. ...
Neutral conductor overheating in a three-phase four-wire system is a zero-sequence problem, so measure harmonic orders first and only then select a filter. A neutral that runs hot while the phases stay comfortably cool is rarely a coincidence. It points to zero-sequence current driven by triplen harmonics, which behaves nothing like a balanced-load calculation predicts. This article follows the or...
Industrial efficiency losses are not always mechanical. A plant can keep every machine healthy and still lose energy, capacity and uptime to harmonics, reactive power and three-phase current imbalance that never appear on a maintenance checklist. VFDs, rectifier-fed equipment and fast-switching electronics make production more efficient while making the network underneath less forgiving. This arti...
Capacitor bank overheating after adding VFDs is a power quality symptom, not a capacitor defect. VFD rectifiers inject harmonic current, the bank offers a low-impedance path at those frequencies, and parallel resonance between the bank and the supply can amplify that current until fuses open, contactors chatter and capacitor cans swell. A capacitor bank supplies reactive power to correct power fac...
Certificate Documentations in Power Quality Selection: Meaning and Guide A procurement engineer receives an Active Harmonic Filter quotation with a compliance certificate attached. The certificate names a product family, but the quotation specifies another voltage, current rating, enclosure layout, ambient condition, and feeder arrangement. The correct question is not “Does the suppli...